Opties        
  ID11 Temp RV druk -99/999 0/4-20mA 0-10V  
     
   
     
 
   
   
   
   
   
     
     
     
     
   
  The ID11 acquisition module transmitt process measurements via RS485 serial links with MODBUS RTU (JBUS) protocol to either a computer based data acquisition system or to the OMS monitoring and recording device. The ID11 accepts up to 4 analog signals such as 0/4.20 mA or 0/2.10 V from temperature, pressure, humidity etc trasmitters. The ID11, further than transmitting the measure of every channel via RS485, it's also able to manage directly the signals of high and low alarm for each channel. Each serial connection is capable of handling a maximum of 15 ID11 modules for a total of 60 measurements of various quantities. Each module includes 4 digital inputs for free voltage contacts and one relay output. The digital inputs can be used to transmit, to the supervision system, information about local devices of the plant as for instance status of protection devices, open doors, lights, etc.. The relay output can be used for a local high or low alarm, via serial line or programmino the ID11 itself, or can be controlled based on the status of a digital input.
 
     
  Specificaties  
     
  Self-extinguishing plastic UL 94 V0  
  4 DIN Modules 70x85 mm, depht 61 mm  
  210 g approx.  
  On OMEGA DIN rail  
  2,5 mm2 screw terminal block  
  24, 110, 230 VAC +/- 10%  
  50 / 60 Hz  
  3 VA max. approx.  
 

4 Analogic inputs, 0/20mA, 4/20mA, 0/10V.
4 Digital inputs

 
  0/4.20 mA: 66 Ω;
0/2.10 V: 120 KΩ
 
  1 relay SPST-NO (5A-AC1, 2A-AC3 / 250 VAC)  
  100000 oper.  
  350 points  
  +/-0,5% fs  
  2 sample per second  
  RS485 insulated  
  MODBUS RTU (JBUS)  
  Programmable from 1200 . 38400 baud  
  0 ... 55°C  
  30 ... 95 RH% without condensation  
  CE, RoHS en WEEE  
 
  Leveringsomvang:    
 
l
l
   
   
 
     
  Opties